Tate Access Floor Panel, ConCore, 1250, HPL

SKU: Tate-CC1250-Bolted (each) Category: Tag:

Tate Access Floor Panel, ConCore, 1250, HPL panels are epoxy-coated solid panels filled with lightweight cement and rated for static design loads of 1250lbs. Fits bolted stringer understructures and are factory-laminated with a high-pressure laminate finish.

To receive an email quote,  select a quantity and click Add to Quote. 

Add to Quote

For assistance contact our sales team at (888) 247-0986 x2 or via email at sales@team-prosoure.com

SKU: Tate-CC1250-Bolted (each) Category: Tag:

Tate Access Floor Panel, ConCore, 1250, HPL panels are epoxy coated unitized shells consisting of a flat steel top sheet welded to a formed steel bottom pan filled with a highly controlled mixture of lightweight cement. Manufactured to exacting tolerances, these non-combustible, rigid, solid panels deliver the ultimate in strength, durability, and acoustic performance. ConCore panels are suitable for almost any application and are factory laminated with HPL. Tate's ConCore 1250 raised access floor panel is intended for commercial applications with a light total load requirement and is engineered to meet Tate Standards per CISCA testing methods.

Key Performance Characteristics

  • Panel weight: 8 lbs/ft² bare
  • All steel welded construction
  • Filled internally with a cementitious core material
  • Protected from corrosion by an epoxy paint finish
  • Class A flame spread rating
  • Non-combustible material
  • System Performance

Tate Standards to CISCA Testing Methods. System Performance Criteria (Tested on Actual Understructure*)

System TypeSystem Weight (lbs/ft2)Static LoadsRolling LoadsImpact Loads
PanelUnderstructureDesign Loads1Minimum
Ultimate Loads
Safety Factor
(min 2.0)2
10 Passes10,000 Passes
ConCore 1250Posilock8.5 lbs/ft21250 lbs2500 lbsPASS1000 lbs800 lbs150 lbs
Bolted Stringer9.5 lbs/ft21250 lbs2500 lbsPASS1000 lbs800 lbs150 lbs

*All tests are performed using CISCA's Recommended Test Procedures for Access Floors with the exception of Design Load

  1. System Design Load is based on a permanent set ≤ 0.010” and is verified by loading panels in accordance with the CISCA concentrated load method but with panels installed on actual understructure instead of steel blocks. (Testing on blocks does not represent the performance of an actual installation.) Ultimate, Rolling, and Impact Load tests are performed using CISCA Test Procedures.
  2. Safety Factor is Ultimate Load divided by Design Load.

Product Information

Tate ConCore 1250 HPL Data Sheet

Tate ConCore Detail 24in With HPL

Manufacturer

Tate Access Floors

Reviews

There are no reviews yet.